The LASS series Addressable Synchronised strobes and sounder-strobes are loop-powered audible and visual alarm device that plug in to System Sensor analogue addressable detector base such as the B501AUS.
Each LASS-series alarm device can be individually activated (addressed) by a fire panel over an analogue addressable loop. In a Pertronic F220 system, the control panel’s loop driver board controls the audible and visual signals. Tones and light flashes from all LASS alarm devices connected to a single loop driver can be synchronised, provided that the loop driver is fitted with firmware version 4.08.00 or later. An F220 loop driver can control two analogue addressable loops. So, all LASS devices on a pair of loops can be synchronised.
Two audible alarm tones can be controlled by the fire panel. These tones indicate alarm Stage 1 (Evacuate) and alarm Stage 2 (Alert). The pair of tones may be configured from any one of four optional two-stage tone-sets. The sounder-strobe’s visual alarm is internally synchronised with the audible alarm.
LASS series alarm devices are compatible with the optional anti-tamper feature on the B501 and compatible detector bases. When activated, the anti-tamper feature inhibits unauthorised removal of the alarm device. Note that if an LASS device is used with a B501AP deep base, there will be a 3-4 mm gap between the device and the mounting surface.
The sounder of component of the Addressable Synchronised Sounder-Strobes (LASS-BSS-NC) is independently certified as compliant with AS ISO 7240.3:2014.
Product Code