20W 24V Amplifier

Pertronic

EVAC20W24V Amplifier

The Pertronic 20 Watts Amplifier (EVAC20W24V) is an evacuation amplifier with integral evacuation tone and message generator and fault detection system. It is designed for use in emergency warning systems with supervised 100 Volt Line distribution systems. The amplifier delivers up to 20 Watts of audio power to the 100 Volt line.

The EVAC20W24V generates an evacuation tone with a voice message as specified in NZS 4512:2010. The amplifier is controlled by the BELL output of a fire alarm panel such as the Pertronic F16e, F100 or F120.

When in standby, the 100 Volt line is connected to the BELL circuit. This allows the fire alarm panel to detect short or open circuit faults on the 100 Volt line. The BELL circuit drives a small dc current through the 100 Volt line, which must be terminated with a suitable end of line resistor. It is important to note that every speaker connected to the supervised 100 Volt Line must be specially designed for emergency warning systems, with each speaker incorporating a DC blocking capacitor. The fault monitoring system also monitors for power supply faults, overload conditions, low power output.

Features

  • Generates the ‘Evacuation’ tone with verbal messages as specified by NZS 4512:2010
  • Designed for connection to the monitored sounder output of an F16e, F100 or F120 Fire Alarm Panel and is activated when the sounder circuit voltage polarity reverses to the ‘Alarm’ state
  • In the ‘Normal’ state, the amplifier draws practically no current (less than 0.2 μA) and appears transparent to the Fire Alarm panel
  • The 100 Vrms line is internally connected to, and monitored by, the panel’s Sounder circuit
  • The amplifier’s 100 Vrms line is short-circuit protected and is capable of driving up to 20W (27.4 Vdc supply) into connected PA loud speakers, eg. Pertronic PSS1 and PSSB401