Pertronic THD-series Thermistor Heat Detectors are conventional indicating heat detectors with fixed alarm temperature thresholds, for use in NZS 4512-compliant fire systems.
Internal electronics in all THD-series detectors are conformally-coated.
Pertronic THD-series Thermistor Heat Detectors are available in two temperature ranges: Blue, 57 °C, and Yellow, 77 °C.
Each detector has a bi-colour indicator LED. When the detector is in the alarm state, the LED glows red. If the detector is wired with incorrect polarity, the LED glows yellow.
Features
- Conventional indicating heat detector with fixed (static) temperature threshold
- Smooth uncluttered design
- Conformally-coated PCB
- Corrosion-resistant materials
- Red LED indication latches ON when an alarm condition is detected
- Remote indicator versions have an output connection for a remote LED indicator (DETREM). The remote indicator latches ON when an alarm condition is detected
- Bi-directional Line In + Line Out terminations
- Terminals on interior versions accept up to 1.5 mm² cable
- Yellow LED indicates reverse polarity connection
- Reverse polarity connection initiates the Defect: High status in Pertronic panels
- In the alarm state, the detector clamps the detection circuit voltage to 2.7 V
- Resistant to false activation caused by vibration or other transient impulses
- Independently tested and certified compliant with NZS 4512:2010